VFD energy savings calculator

Estimate how much energy, money and CO₂ a variable frequency drive saves on a pump or fan compared with valve or damper control — and see exactly how the figures are worked out.

Energy savings

What could a VFD save you?

For centrifugal pumps and fans the affinity laws apply: flow ∝ speed, pressure ∝ speed², power ∝ speed³. Throttling a valve or damper wastes that difference as heat and noise; a drive simply slows the motor down.

SpeedFlowPower
100%100%100%
90%90%73%
80%80%51%
70%70%34%
60%60%22%
ENERGY SAVED / YEAR—kWh
COST SAVED / YEAR—at your tariff
REDUCTION—vs throttled control
CO₂ AVOIDED—per year

Indicative estimate for centrifugal loads, 300 days/year, compared with valve/damper control at ~85% of rated power. Actual savings depend on your duty profile — we'll measure it for you.

How it's calculated

The formulas

For centrifugal pumps, fans and blowers the affinity laws relate speed (N) to flow (Q), head or pressure (H) and shaft power (P):

Q₂ / Q₁ = N₂ / N₁
H₂ / H₁ = (N₂ / N₁)²
P₂ / P₁ = (N₂ / N₁)³

The calculator compares two ways of getting the reduced flow:

Throttled (valve / damper, motor at full speed)
Ethr = Prated × h × D × 0.85

With VFD (motor slowed to the needed speed)
Evfd = Prated × (N%/100)³ × h × D ÷ ηvfd

Savings
ΔE (kWh/yr) = Ethr − Evfd
Cost (₹/yr) = ΔE × tariff
CO₂ (t/yr) = ΔE × 0.71 ÷ 1000
Assumptions

What the numbers mean

SymbolMeaningValue used
PratedMotor ratingSlider (kW)
hRunning hours per daySlider
N%Average speed neededSlider (50–100%)
DOperating days per year300
0.85Power drawn when throttled, as a fraction of ratedTypical for valve/damper control
ηvfdDrive efficiency0.97
0.71Grid emission factor (kg CO₂/kWh)India grid average (CEA)

Worked example

A 22 kW pump running 16 h/day at 80% speed, ₹9/kWh:

Ethr = 22 × 16 × 300 × 0.85 = 89,760 kWh
Evfd = 22 × 0.8³ × 16 × 300 ÷ 0.97 = 55,739 kWh
ΔE = 34,021 kWh/yr → ₹306,186/yr, 24.2 t CO₂

Constant-torque loads (conveyors, compressors, extruders) don't follow the cube law; savings there come mainly from soft starting and matching speed to demand. For an accurate figure we log your actual load profile.

Want a measured savings report?

We log your motor's real load for a week and give you a payback calculation for a VFD retrofit.